Danfoss 80G8280 Ejector Controller

제품 정보
- The EKE 80 Ejector Controller receives input signals from Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
- It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure, thereby decreasing 에너지 소비량.
- The EKE 80 drive controller is suitable for both new and retrofit systems.
- Identify the connectors on the EKE 80 Ejector Controller according to the manual.
- Connect the necessary input signals from the Danfoss controllers or PLC to the designated connectors on the EKE 80.
- Ensure proper power supply connection to the controller.
- Follow the specific wiring instructions for connecting HP/LP ejectors and modulating control valves.
- 시스템이 제대로 작동하는지 테스트하십시오.
- Refer to the manual for detailed information on connecting various components to the EKE 80 Ejector Controller.
- Use the specified connectors and follow the wiring guidelines provided.
- Power on the EKE 80 Ejector Controller.
- Set the desired parameters using the interface connected to the controller.
- Monitor the system performance and make adjustments as needed for optimal efficiency.
소개
- The EKE 80 Ejector Controller receive inputs signals from the Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC.
- It can control multiple HP/LP ejectors and up to 2 modulating control valves to facilitate the ‘lift’ of the MT suction pressure and thereby decrease energy consumption.
- The EKE 80 drive controller is suitable for both new and retrofit systems.
신분증

응용 프로그램 예ample

일반 기능 및 경고
플라스틱 하우징 기능
- EN 60715를 준수하는 DIN 레일 장착
- IEC 0-60695-11에 따른 자기 소화성 V10 및 IEC 960-60695-2에 따른 12°C에서 백열/열선 테스트
- 볼 테스트: IEC 125-60730에 따라 1°C. 누설 전류: IEC 250에 따라 ≥ 60112V
기타 기능
- 작동 조건 CE: -20T60 / UL: 0T50, 90% RH 비응축
- 보관 조건: -30T80, 90% RH 비응축
- Class I 및/또는 II 기기에 통합 가능
- 보호 지수: 전면 커버에만 IP40
- 절연 부품 전체의 전기적 스트레스 기간: 길다
- 오염도 2의 환경에서 사용하기 적합합니다.
- 내열성 및 내화성 범주: D
- vol에 대한 면역tage surges: category II, category III for versions without display
- 소프트웨어 클래스 및 구조: 클래스 A
규정 준수
CE 마크
- 본 제품은 다음 EU 표준을 준수하도록 설계되었습니다.
- 낮은 볼륨tag전자 지침 LVD 2014/35/EU:
- EN60730-1: 2011 (가정용 및 유사 용도의 자동 전기 제어. 일반 요구 사항)
- EN60730-2-9: 2010 (온도 감지 제어에 대한 특별 요구 사항)
- 전자기 호환성 EMC 지침 2014/30/EU:
- EN 61000-6-3: 2007 +A1: 2011 (주거, 상업 및 경공업 환경에 대한 배출 표준)
- EN 61000-6-2: 2005(산업 환경에 대한 내성)
- RoHS 지침 2011/65/EU 및 2015/863/EU:
- EN50581 : 2012
- 중국 RoHS
UL 승인: - UL file E31024
일반 경고
- 이 설명서에 설명되지 않은 모든 사용은 잘못된 것으로 간주되며 제조업체에서 승인하지 않습니다.
- 장치의 설치 및 작동 조건이 특히 공급량과 관련하여 설명서에 지정된 조건을 준수하는지 확인하십시오.tag전자 및 환경 조건
- This device contains live electrical components therefor,e all the service and maintenance operations must be performed by qualified personnel
- 해당 장치를 안전 장치로 사용할 수 없습니다.
- 장치의 잘못된 사용으로 인한 부상이나 손상에 대한 책임은 전적으로 사용자에게 있습니다.
설치 경고
- 권장 장착 위치: 수직
- 설치는 해당 국가의 현지 표준 및 법률에 따라 실행되어야 합니다.
- 항상 주 전원 공급 장치에서 장치를 분리한 상태에서 전기 연결을 수행하십시오.
- 장치에 대한 유지 관리 작업을 수행하기 전에 모든 전기 연결을 분리하십시오.
- 안전상의 이유로 기기는 접근 가능한 충전 부품이 없는 전기 패널 내부에 장착되어야 합니다.
- 기기를 지속적으로 물 분사에 노출시키지 마시고, 상대 습도가 90%가 넘는 곳에 두지 마세요.
- Avoid exposure to corrosive or pollutant gases, natural elements, environments where explosives or mixes of fiammable gases are present, dust, strong vibrations or shock, large and rapid fluctuations in ambient temperature that in combination with high humidity,y can condensate, strong magnetic and/or radio interference (e.g., transmitting antennae)
- 부하 연결 시 각 릴레이 및 커넥터의 최대 전류에 주의하세요.
- Use cable ends suitable for the corresponding connectors. After tightening the screws of the connectors, slightly tug the cables to check their tightness
- 적절한 데이터 통신 케이블을 사용하십시오. 사용되는 케이블 종류와 권장 설정은 설치 가이드 “MCX 하드웨어 네트워크 사양”을 참조하세요.
- 프로브 및 디지털 입력 케이블의 경로를 최대한 줄이고 전원 장치를 둘러싸는 나선형 경로를 피하십시오. 전자기 노이즈를 방지하려면 유도성 부하 및 전원 케이블과 분리하세요.
- 정전기 방전을 방지하기 위해 보드에 장착된 전자 부품을 만지거나 거의 만지지 마십시오.
- 해당 상품은 인터넷에 직접 노출되기에는 적합하지 않습니다.
면책조항: 전문가용으로만 사용
- 이 제품은 필요한 전문 지식과 자격을 갖춘 전문가에게만 공급하고 사용하도록 되어 있으므로 영국 PSTI 규정의 적용을 받지 않습니다.
- Any misuse or improper handling may result in unintended consequences. By purchasin이 제품을 사용하거나 이용하는 것은 해당 제품이 전문가용으로만 사용 가능하다는 점을 인지하고 동의하는 것으로 간주됩니다.
- Danfoss는 제품의 부정확하거나 부적절한 사용으로 인해 발생하는 손해, 부상 또는 불리한 결과("손상")에 대해 어떠한 책임도 지지 않으며, 귀하는 제품의 부정확하거나 부적절한 사용으로 인해 발생하는 모든 손해에 대해 Danfoss를 면책하는 데 동의합니다.
기술 사양
전원 공급
- 21 – 265 V AC, 50/60 Hz. Maximum power consumption: 15 W. Insulation between power supply and the extra-low voltag전자: 강화
- 40~230V 직류
통신 인터페이스
| 인터페이스 | 사용 | 커넥터 라벨 | 인위적인 데이터 |
| 캔버스 | 사용자 인터페이스, MCX 컨트롤러, 서비스 도구 등에 연결하기 위한 필드버스 | CAN-RJ 가능 | Physical layer according to ISO 11898-2 High Speed CAN bus Frame format according to CAN 2.0B specification
Transceiver not isolated (power supply has reinforced isolation) |
| USB 장치 | 향후 사용을 위해 준비됨 | USB-DEV | 플러그: 미니 B형 |
| USB 호스트 | For connection to the Flash drive for application software update, datalogging and service | USB-H | 플러그: 유형 A |
| RS485-1
RS485-2(MCX20B2만 해당) |
Communication bus to BMS (e.g. Modbus slave), service tools, smart devices (e.g. Modbus master), RS485-1 can be polarized as master from the application | RS485-1 RS485-2 | Physical layer according to EIA 485 Ref3
Provide 500 V peak transient galvanic isolation |
| 이더넷 | 을 위한 web server functionality, integration (e.g. Modbus TCP)
NOTICE! Do not route cable outside of buildings. Connect only to IT equipment compliant with EN 60950 or EN 62368 (Information technology equipment. Safety. General requirements) |
이더넷 | 인터페이스 유형: 10 BASE-T 및 100 BASE-TX, IEEE 802.3.
MDI-X (Automatic medium- dependent interface crossover) |
와이어 길이
| 인터페이스 | 최대 와이어 길이(m) | 최대. 전송 속도(bps) | 최소 와이어 크기 |
| 이더넷 | 100 | 10/100 분 | |
| 1000 | 50천 | 와이에스지18 | |
| 500 | 125천 | 와이에스지22 | |
| 캔버스 | 250 | 250천 | 와이에스지24 |
| 80 | 500천 | 와이에스지26 | |
| 30 | 1분 | 와이에스지26 | |
| RS485 | 1000 | 125천 | 와이에스지22 |
| 신호 배선 | 30 |
연결
| 커넥터 | 유형 | 치수 |
| 맨 위 판자 | ||
| 디지털 입력 1 커넥터 | 3방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 아날로그 입력 11-14 커넥터 | 7방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 디지털 입력 2 커넥터 | 3방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 디지털 입력 3 커넥터 | 3방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 디지털 입력 4 커넥터 | 3방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 디지털 입력 5-8 커넥터 | 5방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 바닥 판 | ||
| 디지털 출력 1-5 커넥터 | 10방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 디지털 출력 6 커넥터 | 6방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 이더넷 커넥터 | 8/8 웨이 RJ 45 플러그 유형 | |
| USB 호스트 커넥터 | USB 타입 A | |
| 아날로그 입력 1-5 커넥터 | 11방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 전원 공급 커넥터 | 2방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 디지털 출력 9-13 커넥터 | 10방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| 아날로그 출력 1-2 커넥터 | 8방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| RS485 -2 커넥터 | 3방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| RS485-1커넥터 | 3방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| CAN 커넥터 | 4방향 나사 플러그인 커넥터 유형 | • pitch 5 mm
• section cable 0.2 – 2.5 mm² |
| CAN-RJ 커넥터 | 6/6방향 전화 RJ12 플러그 유형 | |
| USB DEV 커넥터 | USB 미니 B | |
사용자 인터페이스
LCD 디스플레이
- 디스플레이 모드: STN 블루 투과형
- back-light: white LED back-light, adjustable via software
- display format: 128 x 64 dots
- active visible area: 58 x 29 mm
- contrast: adjustable via software
디스플레이 설정 조정
- Settings of the LCD display like contrast and brightness, might need to be adjusted due to external ambient factors.
- Press and release the Enter and X key after powering on to access the BIOS menu and select the DISPLAY menu.
- Use UP and DOWN arrow keys to adjust the contrast or the brightness of the display at the desired level.
외부 디스플레이

차원
Dimension EKE 80

연결, 낮은 수준
경고
공급량tage of AI may not share the signal with other controllers

연결, 상위 레벨

| AI | 상표 | 설명 | 신호 유형 choice Via software or fieldbus | 기본 | 모드버스 등록하다 | 논평 |
| AI-01 | AI1 | Capacity Reference | 0 ~ 10V
0 ~ 5V 2 ~ 10V 0–20mA 4–20mA |
0 ~ 10V | 17902 | 최대 13.5V 입력 볼륨tage.
볼륨을 연결하지 마십시오tage sources without current limitation (overall 80 mA) to analog inputs while unit is not powered |
| AI-02 | AI2 | ICAD Ejector Mode Feedback | 0–20mA
4–20mA |
4–20mA | 17903 | |
| AI-03 | AI3 | ICAD Bypass Mode Feedback | 0–20mA
4–20mA |
4–20mA | 17904 | |
| AI-04 | AI4 | 압력 트랜스미터 | 0 ~ 5V
0 ~ 10V 0–20mA 4–20mA |
4–20mA | 17905 | |
| AI-05 | AI5 | 온도 센서 | 0–10 V NTC–10K PT1000 | PT1000 | 17906 | |
| AI-06 | 없음 | Not available for customer use | 없음 | 없음 | 예약된 | 예약된 |
| AI-07 | ||||||
| AI-08 | ||||||
| AI-09 | ||||||
| AI-10 | ||||||
| AI-11 | AI11 | Not used in logic. User configurable IO | None NTC–10K PT1000 0–5 V
0 ~ 10V 2 ~ 10V 0–20mA 4–20mA |
없음 | 17907 | 최대 13.5V 입력 볼륨tage.
볼륨을 연결하지 마십시오tag장치에 전원이 공급되지 않는 동안 아날로그 입력에 대한 전류 제한(전체 80mA) 없는 소스 |
| AI-12 | AI12 | 17908 | ||||
| AI-13 | AI13 | 17909 | ||||
| AI-14 | AI14 | 17910 | ||||
| AI-15 |
없음 |
Not available for customer use |
없음 |
없음 |
예약된 |
예약된 |
| AI-16 | ||||||
| A0 | 상표 | 설명 | 신호 유형 선택 | 기본 | 모드버스 등록하다 | 논평 |
| A0-01 | AO1 | ICAD Ejector Mode Request OD | 0 ~ 10V
2 ~ 10V |
0 ~ 10V | 18102 | Analog Outputs galvanically isolated, minimum load 1K Ω (10 mA) for each output |
| A0-02 | AO2 | ICAD Bypass Mode Request OD | 0 ~ 10V
2 ~ 10V |
0 ~ 10V | 18103 | |
| A0-03 | 없음 | Not available for customer use | 없음 | – | 예약된 | 예약된 |
| A0-04 | ||||||
| A0-05 | ||||||
| A0-06 |
| DI | 상표 | 설명 | 신호 유형 선택 | 기본 | 모드버스 등록하다 | 논평 |
| 디-01 | DI1 | Not used in logic, User configurable IO | 24 V or 230 V Depending on port used. See upper level diagram |
– |
17498 | 24 V Opto isolated, 24 V AC 50/60 Hz or 24 V DC Rated current: 5 mA @ 24 V AC
230 V Opto isolated, 86–265 V AC / 50/60 Hz, Reinforced isolation, Rated current: 2,5 mA @ 265 V AC |
| 디-02 | DI2 | Not used in logic, User configurable IO | 17499 | |||
| 디-03 | DI3 | Not used in logic, User configurable IO | 17500 | |||
| 디-04 | DI4 | Not used in logic, User configurable IO | 17501 | |||
| 디-05 | DI5 | Suction Flow Control | Dry contact and/or 24 V AC |
– |
17503 | As the inputs are not isolated, caution has to be used when applying 24 V AC: the same polarity of the supply MUST always be used on COM/GND connection. Counting function with max frequency of 16.6 Hz (30 ms minimum pulse time) |
| 디-06 | DI6 | Ejector Mode Signal Error | 17504 | |||
| 디-07 | DI7 | Bypass Mode Error Signal | 17505 | |||
| 디-08 | 없음 | Not used in logic | 없음 | 없음 | 예약된 | 예약된 |
| 디-09 | ||||||
| 디-10 | ||||||
| 디-11 | ||||||
| 디-12 | ||||||
| 디-13 | ||||||
| 디-14 | ||||||
| 디-15 | ||||||
| 디-16 | ||||||
| 디-17 | ||||||
| 디-18 | ||||||
| 디-19 | ||||||
| 디-20 | ||||||
| 디-21 | ||||||
| 디-22 |
| DO | 상표 | 설명 | 신호 유형 선택 | 기본 | 모드버스 등록하다 | 논평 |
| 도-01 | DO1 | 알람 출력 | – | 17702 | 저항성 부하의 경우 5A 250V AC – 100,000 사이클
유도 부하의 경우 3A 250V AC – cos(phi) = 100,000인 0.4 사이클 UL: 3 A resistive, 250 V AC, 100,000 cycles; 1/8 hp, 125/250 V AC, 30,000 cycles; C300 pilot duty, 125/250 V AC, 30,000 cycles |
|
| 도-02 | 없음 | Not used in logic | 없음 | 없음 | 예약된 | |
| 도-03 | DO3 | User-assigned Ejector |
Not assigned Ejector 1 이젝터 2 이젝터 3 이젝터 4 Ejector 5-8 expansion module only |
할당되지 않음 | 17703 | Internal Solid State Relay for Industrial Ejector Coils:
15–280 Vrms, 0.5 A UL: Making current: 7 A, Breaking current: 0.7 A, Pilot duty (cos θ 0.35), 240 V AC, N.O 중요한: For a Multi-Ejector, an external Solid State Relay is necessary between the assigned DO and the Multi-Ejector solenoid coils that meet the following specifications: Leakage current suppression. At least 2 A rating for both 110 V and 230 V Multi-Ejector coils. 중요한: Ejectors 5 to 8 can only be assigned to an extension module. An extension module is the same controller device as this device except that it is user-configured/ defined as an extension module for control of extra Ejectors, i.e., When there are more than 4 Industrial Ejectors. |
| 도-04 | DO4 | User-assigned Ejector | 할당되지 않음 | 17704 | ||
| 도-05 | DO5 | User-assigned Ejector | 할당되지 않음 | 17705 | ||
| 도-06 | DO6 | User-assigned Ejector | 할당되지 않음 | 17706 | ||
| 도-07 | 없음 | Not used in logic | 없음 | 없음 | 예약된 | 없음 |
| 도-08 | ||||||
| 도-09 | ||||||
| 도-10 | ||||||
| 도-11 | ||||||
| 도-12 | ||||||
| 도-13 | ||||||
| 도-14 | ||||||
| 도-15 | ||||||
| 도-16 | ||||||
| 도-17 | ||||||
| 도-18 | ||||||
| 도-19 | ||||||
| 도-20 |
연락하다
- Danfoss A / S
- 기후 솔루션
- 댄포스닷컴
- +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals cataloques descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding it and to the extent, explicit reference is made in a quotation or order confrmation. Dantoss cannot accept any responsibility for possible errors in catalogues, brochures, videos, and other material. Janfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered, provided that such alterations can be made without changes to form, fit or function of the product.
이 자료의 모든 상표는 Danfoss A/S 또는 Danfoss 그룹 회사의 재산입니다. Danfoss 및 Danfoss 로고는 Danfoss A/S의 상표입니다. 모든 권리는 보호됩니다.

자주 묻는 질문
Q: Can the EKE 80 Ejector Controller be used with third-party controllers?
A: The EKE 80 is designed to work with Danfoss controllers AK-PC 782A/AK-PC 782B or a PLC. Compatibility with third-party controllers may vary, it is recommended to consult with Danfoss support for further information.
Q: What is the maximum wire length supported for Ethernet connection?
A: The maximum wire length for Ethernet connection is 100 meters.
문서 / 리소스
![]() |
Danfoss 80G8280 Ejector Controller [PDF 파일] 설치 가이드 080G5022, 080R9502, 80G8280, 80G8280 Ejector Controller, 80G8280, Ejector Controller, Controller |