심플렉스 4090-9001

Simplex 4090-9001 IAM IDNET 감독형 개별 주소 지정 가능 모듈 사용자 설명서

모델: 4090-9001 | 브랜드: 심플렉스

1. 서론

The Simplex 4090-9001 Individual Addressable Module (IAM) is a supervised device designed for use with Simplex IDNET fire alarm control panels. This module provides supervised monitoring of a normally open or normally closed contact, allowing the fire alarm system to monitor various external devices such as flow switches, tamper switches, or other alarm initiating devices. Its compact design and addressable capabilities ensure efficient and reliable integration into a comprehensive fire detection and alarm system.

This manual provides essential information for the proper installation, operation, and maintenance of the 4090-9001 IAM. Please read all instructions carefully before proceeding with installation or operation.

2. 안전 정보

Always adhere to local codes, ordinances, and regulations when installing and operating this device. Failure to do so may result in property damage, injury, or death. Only qualified personnel should install and service this equipment.

일반적인 예방 조치:

Simplex 4090-9001 module with installation instructions sheet

Figure 2.1: Simplex 4090-9001 module shown with its installation instructions sheet, highlighting the importance of reviewing all documentation before installation.

3. 설정 및 설치

The 4090-9001 IAM is designed for easy installation within standard electrical boxes or compatible enclosures. Follow these steps for proper setup.

3.1 물리적 설치

  1. Mount the module in a suitable electrical box or enclosure, ensuring it is securely fastened. The module is designed for indoor dry applications.
  2. Ensure adequate space for wiring and ventilation around the module.

3.2 배선 연결

Refer to the module's label and the specific installation instructions (part number 574-331 Rev G, as indicated on the module) for detailed wiring diagrams. The module features terminals for IDNET input/output and supervised contact connections.

Close-up of Simplex 4090-9001 module label showing wiring terminals

그림 3.1: 전면 view of the Simplex 4090-9001 module, clearly showing the IDNET input/output terminals (1-4) and the module's model number and revision information.

3.3 주소지정

The 4090-9001 is an addressable module. Its address is set electronically by the Simplex fire alarm control panel during system configuration. Refer to the control panel's programming manual for details on assigning and verifying module addresses.

4. 운영

The Simplex 4090-9001 IAM operates as an interface between a supervised initiating device circuit and the IDNET communication loop of a Simplex fire alarm control panel.

4.1 Supervised Monitoring

The module continuously monitors the connected contact circuit for changes in state (open or closed, depending on configuration) and for fault conditions (e.g., open circuit, short circuit) using an End-of-Line Resistor (EOLR). Upon detecting an alarm condition (e.g., contact closure for a flow switch) or a fault, the module communicates this status change to the fire alarm control panel via the IDNET loop.

5. 유지관리

The Simplex 4090-9001 IAM is designed for reliable, long-term operation with minimal maintenance. However, periodic inspection and cleaning are recommended as part of a comprehensive fire alarm system maintenance program.

5.1 청소

If the module accumulates dust or dirt, gently wipe the exterior with a soft, dry cloth. Do not use abrasive cleaners, solvents, or excessive moisture. Ensure the module is powered down before cleaning.

5.2 검사

During routine system inspections, visually check the module for any signs of physical damage, loose connections, or environmental stress. Verify that the module's status indicator (if present) is operating normally according to the system's operational guidelines.

Simplex 4090-9001 module with UL listed label

그림 5.1: 측면 view of the Simplex 4090-9001 module, showing the UL Listed label, indicating compliance with safety standards.

6. 문제 해결

This section provides guidance for common issues that may arise with the 4090-9001 IAM. For complex problems, contact a qualified Simplex service technician.

문제가능한 원인해결책
Module not recognized by control panel.Incorrect wiring; Address not assigned or incorrect; Faulty module.Verify IDNET wiring (terminals 1-4). Check control panel programming for correct address assignment. Test module with a known good unit if possible.
Supervised circuit shows trouble.Open circuit; Short circuit; Incorrect EOLR; Faulty contact device.Check wiring for breaks or shorts. Verify correct EOLR value and installation. Test the connected contact device.
Module reports false alarms.Intermittent contact closure; Electrical noise; Faulty module.Inspect the connected device for intermittent operation. Check for sources of electrical interference. Consult Simplex technical support.

7. 사양

기인하다세부 사항
상표심플렉스
모델 번호4090-9001
제품 치수9 x 4 x 8 인치
품목 무게2.08 온스
전원Corded Electric (via IDNET loop)
센서 유형Photoelectric (refers to general fire alarm system components, not the module itself which monitors contacts)
경보 종류Audible (refers to general fire alarm system components, not the module itself which monitors contacts)
애플리케이션Indoor Dry Application
호환성심플렉스 IDNET 화재 경보 제어 패널
UL 목록Fire Alarm Equipment Listed

8. 보증 정보

Simplex products are manufactured to high quality standards. For specific warranty terms and conditions, please refer to the warranty statement provided with your purchase or contact Simplex customer service. Keep your proof of purchase for warranty claims.

9. 지원

For technical assistance, product inquiries, or service requests, please contact Simplex customer support or your authorized Simplex distributor. Provide the product model number (4090-9001) and any relevant system information when seeking support.

Manufacturer: Simplex

부품 번호: 4090-9001

한국어: UPC: 753359764849

For additional resources and documentation, visit the official Simplex website or refer to the instruction manual 574-331 Rev G (if available digitally).

관련 문서 - 4090-9001

사전view Simplex 4090-9007 IDNet Signal IAM: 화재 경보 시스템용 주소 지정 가능 모듈
심플렉스 4090-9007 IDNet 신호 개별 주소 지정 가능 모듈(IAM)의 상세 기술 사양 및 기능입니다. 이 모듈은 심플렉스 4100ES, 4010ES, 4100U 및 4008 시리즈 화재 경보 제어 패널에서 향상된 선택적 신호 및 오디오 제어 기능을 제공하도록 설계되었습니다. 배선, 작동 및 설치 정보가 포함되어 있습니다.
사전view Simplex IDNet Signal IAM 설치 지침
Simplex 4090-9007 IDNet 주소 지정 가능 신호 개별 어댑터 모듈(Signal IAM)의 자세한 설치 지침으로, 주소 설정, 클래스 A 및 클래스 B 알림 기기 회로(NAC) 배선 구성, 그리고 장착 절차에 대한 내용을 다룹니다. 이 가이드는 Signal IAM을 화재 경보 제어 패널 및 알림 기기와 통합하는 데 필요한 필수 정보를 제공합니다.
사전view Modulo Direccionable Individual Simplex 4090-9007 IAM de Señal para Paneles de Alarma de Incendios
IAM(Señal Simplex 4090-9007) 모듈에 대한 설명은 4007ES, 4008, 4010ES, 4100ES 및 4100U의 발화 경보 제어 패널에 대한 주변 IDNet 파라 패널입니다. 순차 선택, NAC 감독, UL, ULC, CSFM 및 FM을 통한 오디오 제어 및 제어 기능이 있습니다.
사전view 개별 단방향 모듈 4090-9007 IDNet para Sinalização de Alarme de Incêndio
IAM(Modulo Endereçável Individual) Simplex 4090-9007 IDNet 기술 문서에 대한 자세한 내용은 Simplex 시리즈 4007ES, 4008, 4010ES, 4100ES 및 4100U에 대한 추가 제어 기능을 제공합니다. 문자, 감독 반복, 작동 세부 정보, 전자 장치 및 메카니카의 세부 사항, 실패 요구 사항 및 월 정보를 포함합니다.tag비상 경보 시스템에 대한 정보입니다.