Model: 4090 9116 | Brand: Simplex

1. 서론

This manual provides essential information for the proper installation, operation, and maintenance of the Simplex 4090-9116 Addressable IDNet Isolator. This device is designed to enhance the reliability of fire alarm systems by isolating faults on the Signaling Line Circuit (SLC).

2. 제품 오버view

The Simplex 4090-9116 is an addressable IDNet isolator module. Its primary function is to protect the integrity of the IDNet communication loop by automatically isolating sections of the circuit that develop a short circuit fault. This ensures that other parts of the fire alarm system continue to operate normally, maintaining critical communication and detection capabilities.

When a short circuit is detected, the isolator opens the circuit on both sides of the fault, effectively removing the faulty section from the loop. Once the fault is cleared, the isolator automatically restores the circuit to normal operation. This self-healing capability significantly improves system resilience and reduces downtime during fault conditions.

Simplex 4090-9116 Addressable IDNet Isolator module

그림 2.1: 전면 view of the Simplex 4090-9116 Addressable IDNet Isolator, showing terminal blocks for wiring connections.

3. 안전 정보

경고:

  • Installation and servicing must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).
  • Disconnect all power before installing or servicing this device to prevent electrical shock and/or equipment damage.
  • Ensure proper grounding and wiring to prevent system malfunctions.
  • Do not operate the device outside its specified environmental limits.

4. 설정 및 설치

The 4090-9116 isolator is designed for easy integration into Simplex IDNet fire alarm systems. It typically mounts in a standard 4-inch square electrical box or compatible enclosure.

Simplex 4090-9116 Isolator with packaging and manual

Figure 4.1: The 4090-9116 isolator module shown with its original packaging and accompanying instruction manual.

4.1 장착

  1. Select a suitable location for mounting, ensuring it complies with local fire codes and accessibility requirements.
  2. Mount the isolator module securely within a compatible electrical box or enclosure using appropriate fasteners.

4.2 배선

Connect the IDNet Signaling Line Circuit (SLC) wiring to the designated terminals on the isolator module. Ensure correct polarity and secure connections. Refer to the specific wiring diagrams provided with your Simplex fire alarm control panel and the isolator's included documentation for detailed instructions.

  • Input/Output terminals are clearly marked.
  • Use appropriate wire gauge as specified by system requirements.
  • 전원을 공급하기 전에 모든 연결 상태를 확인하십시오.
Simplex 4090-9116 Isolator inside its cardboard packaging

Figure 4.2: The 4090-9116 isolator module securely placed within its protective cardboard packaging, ready for installation.

4.3 주소지정

The 4090-9116 is an addressable device. Set the unique address for the isolator using the rotary switches or DIP switches on the module, as per your system's addressing scheme. Consult the fire alarm control panel's manual for address assignment procedures.

5. 작동 원리

The Simplex 4090-9116 operates passively within the IDNet SLC. It continuously monitors the circuit for short circuit conditions. In the event of a short circuit:

  • The isolator detects the fault and automatically opens the circuit on both sides of the shorted section.
  • This action prevents the short circuit from affecting the entire SLC loop, allowing other devices on the unaffected sections to continue communicating with the fire alarm control panel.
  • Once the short circuit is resolved, the isolator automatically closes the circuit, restoring full loop communication.

The isolator does not require external power; it draws power directly from the IDNet SLC.

6. 유지관리

The Simplex 4090-9116 isolator is designed for reliable, long-term operation with minimal maintenance. However, regular system checks are recommended as part of a comprehensive fire alarm system maintenance program.

  • 시각적 검사: Periodically inspect the isolator and its wiring for any signs of physical damage, corrosion, or loose connections.
  • 시스템 테스트: Ensure the isolator's functionality is verified during routine fire alarm system testing, as required by NFPA 72 and local codes. This typically involves simulating a fault to confirm proper isolation.
  • 청소: If necessary, gently clean the exterior of the device with a soft, dry cloth. Do not use abrasive cleaners or solvents.

Any maintenance or repair beyond visual inspection and cleaning should be performed by a qualified fire alarm technician.

7. 문제 해결

If a fault is indicated on the fire alarm control panel related to an IDNet SLC, and an isolator is suspected, consider the following:

  • System Fault Indication: If the control panel indicates an SLC fault, identify the specific section of the loop that is isolated. This points to the location of the short circuit.
  • 배선 점검: Verify all wiring connections to the isolator and connected devices for shorts, opens, or ground faults.
  • 장치 오작동: While rare, an isolator itself could malfunction. If all other devices and wiring in the isolated section are confirmed to be fault-free, the isolator may need to be replaced by a qualified technician.
  • 전원 문제: Ensure the fire alarm control panel is providing stable power to the SLC.

Always consult the fire alarm control panel's troubleshooting guide for specific fault codes and resolutions.

8. 사양

기인하다
상표심플렉스
모델 번호4090 9116
부품 번호4090-9116
품목 무게16온스(1파운드)
제품 치수23 x 16 x 18인치(포장 치수)
전원IDNet SLC
배터리가 포함되어 있나요?아니요
배터리가 필요하세요?아니요
제조업체심플렉스
한국어:643485654193
첫 번째 이용 가능 날짜5년 2015월 XNUMX일

Note: Product dimensions listed may refer to shipping package dimensions rather than the device itself.

9. 보증 및 지원

For warranty information and technical support regarding your Simplex 4090-9116 Addressable IDNet Isolator, please contact Simplex customer service or your authorized Simplex distributor. Ensure you have your product model number and any relevant system details available when seeking support.

For general inquiries, you may refer to the official Simplex website or contact their support channels. Always rely on qualified professionals for installation, maintenance, and troubleshooting of fire alarm system components.

관련 문서 - 4090 9116

사전view Simplex 4090-9007 IDNet Signal IAM: 화재 경보 시스템용 주소 지정 가능 모듈
심플렉스 4090-9007 IDNet 신호 개별 주소 지정 가능 모듈(IAM)의 상세 기술 사양 및 기능입니다. 이 모듈은 심플렉스 4100ES, 4010ES, 4100U 및 4008 시리즈 화재 경보 제어 패널에서 향상된 선택적 신호 및 오디오 제어 기능을 제공하도록 설계되었습니다. 배선, 작동 및 설치 정보가 포함되어 있습니다.
사전view 개별 단방향 모듈 4090-9007 IDNet para Sinalização de Alarme de Incêndio
IAM(Modulo Endereçável Individual) Simplex 4090-9007 IDNet 기술 문서에 대한 자세한 내용은 Simplex 시리즈 4007ES, 4008, 4010ES, 4100ES 및 4100U에 대한 추가 제어 기능을 제공합니다. 문자, 감독 반복, 작동 세부 정보, 전자 장치 및 메카니카의 세부 사항, 실패 요구 사항 및 월 정보를 포함합니다.tag비상 경보 시스템에 대한 정보입니다.
사전view Modulo Direccionable Individual Simplex 4090-9007 IAM de Señal para Paneles de Alarma de Incendios
IAM(Señal Simplex 4090-9007) 모듈에 대한 설명은 4007ES, 4008, 4010ES, 4100ES 및 4100U의 발화 경보 제어 패널에 대한 주변 IDNet 파라 패널입니다. 순차 선택, NAC 감독, UL, ULC, CSFM 및 FM을 통한 오디오 제어 및 제어 기능이 있습니다.
사전view Simplex 4090-9116 Aislador de Comunicaciones IDNet Direccionable - Especaciones Técnicas
Documento técnico detallado sobre el Aislador de Comunicaciones IDNet Direccionable Simplex 4090-9116, cubriendo sus características, Operación, ejemplos de installación, especaciones eléctricas y mecánicas para sistemas de Alarma concendios.
사전view Simplex 4090-9101, 4090-9106 모니터 ZAM 설치 지침
Simplex 4090-9101 및 4090-9106 모니터 존 어댑터 모듈(ZAM) 설치 설명서입니다. IDNet 및 MAPNET II 시스템의 기계 설치, DIP 스위치를 통한 주소 설정, 그리고 전기 연결 방법을 다룹니다.
사전view Simplex IDNet Signal IAM 설치 지침
Simplex 4090-9007 IDNet 주소 지정 가능 신호 개별 어댑터 모듈(Signal IAM)의 자세한 설치 지침으로, 주소 설정, 클래스 A 및 클래스 B 알림 기기 회로(NAC) 배선 구성, 그리고 장착 절차에 대한 내용을 다룹니다. 이 가이드는 Signal IAM을 화재 경보 제어 패널 및 알림 기기와 통합하는 데 필요한 필수 정보를 제공합니다.