Chatsworth P5-1C0A5

Chatsworth P5-1C0A5 Switched Vertical eConnect PDU User Manual

Model: P5-1C0A5

1. 서론

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Chatsworth P5-1C0A5 Switched Vertical eConnect Power Distribution Unit (PDU). Please read this manual thoroughly before using the product and retain it for future reference.

2. 안전 정보

Observe the following safety precautions to prevent injury and damage to the PDU or connected equipment:

  • PDU는 모든 지역 및 국가 전기 규정에 따라 자격을 갖춘 담당자가 설치해야 합니다.
  • PDU 케이스를 열지 마십시오. 내부에는 사용자가 수리할 수 있는 부품이 없습니다.
  • PDU는 반드시 접지가 제대로 된 전원에만 연결하십시오.
  • Do not overload the PDU. The total current draw of connected devices must not exceed the PDU's rated capacity (20A).
  • Operate the PDU within its specified environmental conditions, including the maximum ambient temperature of 149°F (65°C).
  • 유지관리나 설치 절차를 수행하기 전에 전원을 분리하세요.

3. 제품 오버view

The Chatsworth P5-1C0A5 is a Switched Vertical eConnect PDU designed for efficient power distribution and remote management in data center environments. It features 24 individually switched 5-20R outlets, a graphical local display, and comprehensive network monitoring capabilities.

Chatsworth P5-1C0A5 Switched Vertical eConnect PDU showing outlets, circuit breakers, and control panel.

이미지 1: 이상view of the Chatsworth P5-1C0A5 PDU. This image displays the vertical PDU with its numerous 5-20R outlets, labeled circuit breakers (CB1, CB2, CB3), and the integrated control panel featuring a graphical display, navigation buttons, Ethernet ports, and a USB port.

주요 구성 요소:

  • L5-20 Input Plug: For connecting the PDU to the main power source.
  • Circuit Breakers (CB1, CB2, CB3): Provide overcurrent protection for groups of outlets. Each breaker has an ON/OFF switch.
  • 5-20R Outlets: Twenty-four (24) individually switched outlets for connecting IT equipment.
  • Graphical Local Display: Provides real-time power monitoring, configuration, and status information directly on the unit.
  • 이더넷 포트: For network connectivity, enabling IP-based remote monitoring and management.
  • USB 포트: Used for firmware updates and configuration backups.
  • 시리얼 포트 : For direct console access and management.

4. 설정

4.1 장착

The P5-1C0A5 is a vertical PDU designed for tool-less mounting in standard server racks. Ensure the rack has appropriate mounting points and sufficient space for the PDU and its connected cables. Refer to your rack's documentation for specific mounting instructions.

4.2 전원 연결

  1. Ensure all circuit breakers on the PDU are in the OFF position.
  2. Connect the PDU's L5-20 input plug to a dedicated 1-Phase, 110-125V, 20A power circuit.
  3. Verify the power source is properly grounded.

4.3 연결 장비

  1. With the PDU still powered off (breakers OFF), connect your IT equipment power cords to the 5-20R outlets on the PDU.
  2. Distribute the load evenly across the PDU's outlets and circuit breaker groups to prevent overloading any single breaker.

4.4 네트워크 연결

For remote monitoring and management, connect an Ethernet cable from your network switch to one of the Ethernet ports on the PDU's control panel. Refer to the PDU's network configuration guide for initial setup of IP addresses and network settings.

5. 운영

5.1 전원 켜기/끄기

  1. After connecting all equipment, switch the main circuit breakers (CB1, CB2, CB3) on the PDU to the ON position.
  2. The graphical local display will illuminate, indicating the PDU is operational.
  3. Individual outlets can be switched ON or OFF via the local display interface or remotely through the network interface.

5.2 Local Display Operation

Use the navigation buttons adjacent to the graphical display to browse through menus, view real-time power metrics (voltage, current, power, energy), and configure basic settings. Consult the detailed eConnect PDU user guide for comprehensive local display functionality.

5.3 원격 모니터링 및 관리

Access the PDU's web interface via its assigned IP address to perform advanced monitoring, configuration, and control. This includes:

  • Real-time power monitoring of the entire PDU and individual outlets.
  • Individual outlet switching and sequencing.
  • Setting up alerts and notifications for power events.
  • User management and security settings.

The PDU also supports serial monitoring for direct console access.

6. 유지관리

6.1 청소

Periodically clean the exterior of the PDU with a soft, dry cloth. Do not use liquid cleaners or solvents. Ensure the PDU is powered off and disconnected from the power source before cleaning.

6.2 펌웨어 업데이트

Chatsworth may release firmware updates to improve performance or add new features. These updates can typically be applied via the USB port or through the network interface. Refer to the Chatsworth support web최신 펌웨어 및 업데이트 지침은 사이트에서 확인하세요.

6.3 환경 고려 사항

The PDU is designed to operate in high ambient temperatures up to 149°F (65°C). Ensure proper airflow around the unit to prevent overheating. Regularly check the operating environment to ensure it remains within specified limits.

7. 문제 해결

7.1 No Power to Outlets

  • Verify the main L5-20 input plug is securely connected to a live power source.
  • Check if the PDU's circuit breakers (CB1, CB2, CB3) are in the ON position. If a breaker has tripped, switch it OFF, wait a few seconds, and then switch it back ON. If it trips again, reduce the load on that breaker.
  • Confirm that individual outlets are switched ON via the local display or remote interface.

7.2 네트워크 연결 문제

  • Ensure the Ethernet cable is securely connected to both the PDU and the network switch.
  • Verify network settings (IP address, subnet mask, gateway) on the PDU are correct.
  • Check network switch port status and connectivity.

7.3 Breaker Trips Repeatedly

A repeatedly tripping breaker indicates an overload condition. Reduce the total current draw of devices connected to that breaker's group of outlets. If the issue persists with a reduced load, contact technical support.

8. 사양

특징사양
모델 번호P5-1C0A5
상표채츠워스
입력 플러그L5-20
입력 Voltage1-Phase, 110-125V
입력 전류20A
아울렛(24) 5-20R Outlets
브레이커스1 x 2P 20A Hydraulic Magnetic Breakers
서지 보호아니요
모니터링Ethernet, IP, Serial, USB, Graphical Local Display
작동 온도최대 149 ° C (65 ° F)
포장 크기 (근사치)82 x 10 x 8 인치
한국어:703957370393

9. 보증 및 지원

For warranty information, technical support, or service inquiries, please contact Chatsworth Products customer service or visit their official web지원팀에 문의하실 때 구매 영수증과 제품 일련번호를 준비해 두세요.

© 2025 Chatsworth Products. All rights reserved.